RW SERIES INSTALLATION MANUAL
PowerFailRestart
When the controller is first powered up, the outputs will be
disabled for a random start delay time (See Section 4.2). The
delay is provided to prevent simultaneous starting of multiple heat
pumps. Once the timer expires, the controller will operate in the
occupied mode until it is commanded to another mode by a facility
management system or a remote thermostat. A restart status
variable is available for indication of this occurrence.
RandomStartDelay
This delay will be used after every power failure, as well as the
first time the compressor(s) is started after the control exits the
emergency shutdown mode. The default time period for the start
delay will be random between 1 and 120 seconds.
CompressorFixedOnDelayTime
The Compressor Fixed On Delay Time will ensure that the
compressor output is not enabled for (90) seconds after the control
receives a call to start the compressor.
CompressorMinimumOnDelay
The compressor minimum on delay will ensure that the compressor
output(s) are enabled for a minimum of (2) minute each time
the compressor output is enabled. This will apply in every
instance except in the event the high-pressure switch is tripped or
emergency shutdown, then the compressor output will be disabled
immediately.
CompressorShortCycleDelayTime
The compressor short cycle time delay will ensure that the
compressor output will not be enabled for a minimum of (5) minutes
after it is disabled. This allows for the system refrigerant pressures
to equalize after the compressor is disabled.
CompressorStageLeadLag
The factory setup software, a facility management system, Service/
Commissioning Tool, or a user interface can be used to select
compressor lead lag option for the compressors. The factory setup
software, a facility management system, Service/Commissioning
Tool, or a user interface must also be used to select the number
of run time hours the compressors will lead before being switched,
the factory default will be 24 hours. The two compressors will still
be staged depending on load when the lead lag option is enabled.
Sequence of Operation
HeatingCycle
During the heating cycle, the reversing valves will be positioned
for heating operation. The thermostat or aquastat will command
the reversing valves “On” for heating. If the compressor short
cycle time delay has been satisfied, the lead compressor will turn
on after the accessory output has been enabled, the low pressure
switches has been verified, and the fixed compressor start delay
timer has been satisfied. When heating is no longer required, the
compressor will be turned off immediately after the compressor
minimum on delay has been satisfied. After the compressor
output is turned off, it will remain off for the time specified in the
compressor short cycle time delay. If the dual compressor option
is selected, the compressors will be sequenced to maintain the
heating setpoint. As the temperature drops below the heating
setpoint and begins to operate in the heating proportional band,
the first stage compressor will be activated. If the first stage
compressor is not able to satisfy the heating demand, the second
stage compressor will be activated by the thermostat or aquastat.
The controller is allowed to operate the heat pump in the heating
mode regardless of the outdoor air temperature.
CoolingCycle
During the cooling cycle, the reversing valves will be positioned for
cooling operation. The thermostat or aquastat will command the
reversing valves “Off” for cooling. If the compressor short cycle
time delay has been satisfied, the lead compressor will turn on after
the accessory output has been enabled, the low pressure switches
has been verified, and the fixed compressor start delay timer has
been satisfied. When cooling is no longer required, the compressor
will be turned off immediately after the compressor minimum on
delay has been satisfied. After the compressor output is turned
off, it will remain off for the time specified in the compressor short
cycle time delay. If the dual compressor option is selected, the
compressors will be sequenced to maintain the cooling setpoint.
As the temperature drops below the cooling setpoint and begins to
operate in the cooling proportional band, the first stage compressor
will be activated. If the first stage compressor is not able to satisfy
the cooling demand, the second stage compressor will be activated
by the thermostat or aquastat. The controller is allowed to operate
the heat pump in the cooling mode regardless of the outdoor air
temperature.