RW SERIES INSTALLATION MANUAL
AntiShortCycle
HighPressureProtection
LowPressureProtection
AdvancedFreezeDetectionSetpoint
RandomStart
Displayfordiagnostics
ResetLockoutatdisconnect
Intelligentresetforfieldinstalledflowswitches
1Accessoryoutput
OptionalDDCcontroladd-on
CompressorLead/Lag
CompressorCurrentSwitches
FieldSelectableOptions
FreezeDetectionSensingSelect(DI-4andDI-5)
The freeze detection temperature sensing selection inputs allow
the user to adjust the setpoints. The source sensors are wired to
inputs AI-3 and AI-4 while the load sensors are wired to inputs AI-5
and AI-6. The setpoints for both, the load and source, are factory
set for 30°F. In order to change the setpoint to 15°F on the source,
remove the jumper wire from DI-4 (wire #56). The load setpoint can
be changed by removing the jumper wire from DI-5 (wire #55).
AccessoryOutput(DO-4)
The accessory Output will be energized 90 seconds prior to
the lead compressor output being energized. When the lead
compressor output is turned off the accessory output will be
deactivated immediately. The output is selectable for normally
open or normally closed operation through the unit mounted user
interface or from a building automation system.
ControlandSafetyFeatures
EmergencyShutdown
The emergency shutdown mode can be activated by a command
from a facility management system or a closed contact on DI-
2. The default state for the emergency shutdown data point is off.
When the emergency shutdown mode is activated, all outputs will
be turned off immediately and will remain off until the emergency
shutdown mode is de-activated. The first time the compressor
starts after the emergency shutdown mode has been de-activated,
there will be a random start delay present.
LockoutMode
Lockout mode can be activated by any of the following fault signals:
refrigerant system high pressure, refrigerant system low pressure,
heating freeze detection, cooling freeze detection, and compressor
current sensor. When any valid fault signal remains continuously
active for the length of its recognition delay, the controller will
go into fault retry mode, which will turn off the compressor. After
the Compressor short cycle delay, the compressor will attempt
to operate once again. If three consecutive faults are recognized
during a single heating or cooling demand, the unit will go into
lockout mode, turning off the compressor and enabling the alarm
Control Features
output until the controller is reset. The fault count will automatically
reset when the heating or cooling command becomes satisfied. If
a fault occurs on a dual compressor unit, the other compressor will
continue to operate based on the heating or cooling demand. The
lockout condition can be reset by powering down the controller, by
a command from the facility management system, or by holding
both the enter and escape keys on the optional user interface.
ReversibleChillerAdvancedFreeze
DetectionSystem
The reversible chiller source and load heat exchangers are protected
by a multi-sourced temperature logic strategy. The temperature logic
is based upon the refrigerant temperature sensed as the refrigerant
is about to enter the heat exchanger; while entering and leaving
water temperatures are being used as correlating factors. The
detection scheme is shown as basic and advanced algorithms.
BasicFreezeDetectionOperation:“Comp1orComp2
Freeze”Alarm
This alarm can be triggered by one of two detection schemes.
HardLimitFreezeDetection
If the refrigerant temperature drops below the freeze detection
setpoint by 1.8°F, the associated compressor is locked out
immediately regardless of any other factors and requires a
manual reset. NOTE:ThisLockoutproducesa“Comp1or
Comp2Freeze”errorontheMUIdisplay.
FreezeDetection
The refrigerant temperature is compared to the freeze detection
setpoint (15°F [antifreeze] or 33°F [water] field selectable), and
if the temperature falls below the setpoint for 30 continuous
seconds, the associated compressor will be halted. This
function becomes enabled after the first two minutes of
compressor operation. Three such events in 60 minutes will
trigger a compressor lockout that requires a manual reset.
NOTE:ThisLockoutproducesa“Comp1orComp2
Freeze”errorontheMUIdisplay.
Inadditiontotheabove:
Entering Water Temperature Influence
If the entering water temperature of the evaporative heat
exchanger is within 10°F of the freeze setpoint, the previously
mentioned two minute delay will be eliminated. This allows the
freeze detection to operate immediately when the compressor
starts based on entering water temperature.
Leaving Water Temperature Influence
If the leaving water temperature of the evaporative heat
exchanger is within 10°F of the freeze setpoint, the previously
mentioned 30 second delay will begin to be proportionately
reduced, ending at a 1 second delay when the leaving water
temperature is 1.5°F above the freeze setpoint.